GA2-B0-26-610-1C-DC [Carling Technologies]

Magnetic Circuit Breaker,;
GA2-B0-26-610-1C-DC
型号: GA2-B0-26-610-1C-DC
厂家: Carling Technologies    Carling Technologies
描述:

Magnetic Circuit Breaker,

电路保护
文件: 总10页 (文件大小:1599K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
G-  
G-Se  
riesSeries  
DIN-RAIL CIRCUIT BREAKER  
The G-Series hydraulic-magnetic circuit breaker insures maximum protection by integrating wiping contacts  
for longevity; a common trip linkage between poles; a unique terminal bus connection system; and optional  
integrated auxiliary switch. It is also suitable for reverse feed and provides finger safe terminals. This DIN rail  
mount circuit breaker accommodates either a 35mm x 7.5mm, or a 35mm x 15mm symmetrical din rails.  
G-Series DIN Rail Circuit Breaker:  
UL 489 Listed: 1 to 3 poles; 1-50 Amps; 125 VDC, 240 VAC;  
UL 1077 Recognized: 1 to 4 poles; 0.1-63 Amps; 80 VDC, 240 VAC/480VAC; cUL, TUV, CSA & CCC.  
Resources:  
Configure a Complete Part  
Download CAD & Sales Drawing  
Product Highlights:  
•ꢀ DINꢀRailꢀMounting  
•ꢀ ULꢀ489ꢀListed  
Typical Applications:  
•ꢀ RenewableꢀEnergy  
•ꢀ Telecom  
•ꢀ ULꢀ1077ꢀRecognized,ꢀcUL,ꢀTUV,ꢀCSAꢀ&ꢀCCCꢀ  
•ꢀ WipingꢀContacts  
•ꢀ ControlꢀPanels  
•ꢀ IndustrialꢀAutomationꢀControls  
•ꢀ CommonꢀTripꢀLinkageꢀBetweenꢀPoles  
•ꢀ OptionalꢀIntegratedꢀAuxiliaryꢀSwitch  
Carling Technologies, Inc.  
60 Johnson Avenue, Plainville, CT 06062  
Email: sales@carlingtech.com  
Application Support: team2@carlingtech.com  
Phone: 860.793.9281 Fax: 860.793.9231  
www.carlingtech.com  
|
G-Series Circuit Breaker - DIN Rail – Design Features  
2
G-Series  
DESIGN FEATURES  
TERMINAL BARRIERS  
Meet UL 489 Spacing Requirements  
DIN RAIL  
4.56 in  
[115.87 mm]  
MOUNTING  
Snap on Back Panel  
Rail Mounting for  
either 35 x 7.5 mm  
or 35 x 15 mm  
2.167 in  
[55.04 mm
OPTIONAL AUXILIARY SWITCH  
DIN RAIL LOCK  
Provides Breaker Status Indication  
Secures Circuit Breaker to the DIN Rail  
Auxiliary Switch with Internal Connector  
Example Plugs:  
Spring clamp terminals  
Screw terminals  
Screw terminals 45° angle  
Internal connector  
Dimensions in mm  
Advantages:  
Wire size solid wire  
0.2 - 1.5 mm ꢀ  
0.2 - 2.5 mm ꢀ  
Wire size stranded wire  
- Pre-wiring is possible  
- Easy interchangeable  
- Time saving solution  
- Various connection methods  
- Many different plugs  
Wire size stranded wire with ferrule 0.25 - 1.5 mm ꢀ  
Wire stripping length  
10 mm  
The auxiliary contact with internal connector can be used with Phoenix Combicon plugs. Phoenix item  
number internal connector: 1753453. The circuit breaker is standard delivered without plugs.  
*Manufacturer reserves the right to change product specification without prior notice.  
Email: sales@carlingtech.com Application Support: team2@carlingtech.com  
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com  
|
3
G-Series Circuit Breaker - DIN Rail – General Specifications  
Electrical Tables  
Table A: Lists UL Recognized, CSA Accepted and TUV Certified capabilities as a Component Supplementary Protector.  
G-SERIES TABLE A: COMPONENT SUPPLEMENTARY PROTECTORS  
Voltage  
Current Rating Short Circuit Capacity (Amps)  
Circuit  
Max  
Rating  
80  
240  
240  
480  
Minimum  
Full Load  
Amps  
Without Backup Fuse  
Application Codes  
Configuration  
Frequency Phase  
Poles  
UL/CSA  
3000  
3000  
3000  
1500  
TUV  
UL  
CSA  
DC  
---  
1
1
1
2
3
.1 - 63  
.1 - 63  
.1 - 63  
.1 - 63  
1500  
1500  
1500  
TC1, OL1, U1 TC1, OL1, U1  
TC1, OL1, U1 TC1, OL1, U1  
TC1, OL1, U1 TC1, OL1, U1  
50 / 60  
50 / 60  
50 / 60  
Series  
1
3
415V, 1000 TC1, OL1, U1 TC1, OL1, U1  
Table B: Lists UL Listed (489) configuration and performance capabilities.  
G-SERIES TABLE B: UL 489 LISTED BRANCH CIRCUIT BREAKERS  
Interrupting Capacity  
(Amps RMS)  
Circuit  
Voltage  
Current Rating  
Full Load Amps  
1 - 50  
Configuration  
Max Rating Frequency Phase  
Poles  
80  
DC  
---  
---  
1
1
5000  
5000  
5000  
5000  
125  
DC  
2
1 - 50  
120  
50 / 60  
50 / 60  
1
1 - 50  
Series  
120 / 240  
1
1 - 31  
1 - 50  
240  
50 / 60  
1
1
1 - 25  
5000  
1
One pole out of the three poles must be a neutral break.  
Electrical  
Mechanical  
Maximum Voltage  
AC: 240VAC (single pole),  
Endurance  
10,000 ON-OFF operations @ 6 per  
minute; with rated current & voltage.  
All G-Series circuit breakers will  
trip on overload, even when actuator  
is forcibly held in the ON position.  
The operating actuator moves  
480VAC (3 poles, additional pole  
shall be dedicated for neutral break)  
DC: 80VDC (single pole & multipole)  
0.1 – 63A. Other ratings available,  
see Ordering Scheme.  
Trip Free  
Current Rating  
Trip Indication  
Auxiliary Switch Rating (optional) Integrated, load side.  
SPST, 3A – 125VAC, 2A – 30VDC.  
Auxiliary switch senses the on & off  
position of circuit breaker handle,  
as well as contact arm position.  
Switch connections are screw  
positively to the OFF position when  
an overload causes the breaker to  
trip. With mid-trip, the handle moves  
to the mid position on electrical trip  
of the circuit breaker. With mid trip  
handle with alarm switch, handle  
moves to the mid position and the  
alarm switch actuates when the  
circuit breaker is electrically tripped.  
terminals.  
Insulation Resistance  
Dielectric Strength  
Minimum of 100 Megohms at 500 VDC  
UL, CSA: 1960 V 50/60 Hz for one  
minute between all electrically  
isolated terminals. G-Series circuit  
breakers comply with the 8mm  
spacing and 3750V 50/60 Hz dielectric  
requirements from hazardous  
voltage to operator accessible  
surfaces, between adjacent poles  
and from main circuits to auxiliary  
circuits per Publications EN 60950  
and VDE 0805.  
Physical  
Number of Poles  
Weight  
1 pole ≤ 63A, 2 poles ≤ 63A per pole  
Approx.172 grams/pole ( 4.13 oz).  
Housing: Black  
Standard Colors  
Environmental  
Designed in accordance with requirements of specification  
MIL-PRF-55629 & MIL-STD-202 as follows:  
Shock  
Withstands 100 Gs, 6ms sawtooth  
while carrying rated current per  
Method 213, Test Condition “I”.  
Instantaneous and ultrashort curves  
tested @ 90% of rated current.  
Withstands 0.060” excursion from  
10-55 Hz & 10 Gs 55-500 Hz, @  
rated current per Method 204C, Test  
Cond. A. Instantaneous & ultrashort  
curves tested @ 90% of rated  
current.  
Method 106D, i.e., ten 24-hour  
cycles @ +25°C to +65°C, 80-98% RH.  
Method 101, Condition A (90-95%  
RH @ 5% NaCl Solution, 96 hrs).  
Method 107D, Condition A (five cycles  
@ -55°C to +25°C to +85°C to +25°C).  
Resistance, Impedance Values from Line to Load Terminal -  
based on series trip circuit breaker.  
RESISTANCE, IMPEDANCE VALUES  
from Line to Load Terminals  
(Values Based on Series Trip Circuit Breaker)  
1000  
Vibration  
CURRENT  
(AMPS)  
TOLERANCE  
(%)  
100  
10  
0.10 - 5.0  
5.1 - 20.0  
20.1 - 63.0  
15  
25  
35  
O
H
M
S
1
Moisture Resistance  
Salt Spray  
0.1  
0.01  
Thermal Shock  
0.001  
0.01  
0.1  
1
10  
100  
Operating Temperature -40°C to +85°C  
AMPERE RATING  
Email: sales@carlingtech.com Application Support: team2@carlingtech.com  
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com  
|
4
G-Series Circuit Breaker - DIN Rail – UL Recognized – Ordering Scheme  
G A 1 B 0 24 620 1 1 D C  
8
9
10  
Rating  
11  
Agency  
Approval  
1
2
3
4
5
6
7
Terminal  
Actuator  
Color &  
Legend  
Series  
Actuator  
Poles  
Circuit  
Aux/Alarm  
Switch  
Frequency  
& Delay  
Current Rating  
1 SERIES  
G
8 TERMINAL  
1
Screw Terminal  
2 ACTUATOR  
9 ACTUATOR COLOR & LEGEND  
A
S
Handle, one per pole  
Actuator Color  
White  
I-O  
A
C
F
H
K
M
P
ON-OFF  
Dual  
Legend Color  
Black  
Mid-Trip Handle, one per pole  
B
D
G
J
1
2
3
4
5
6
7
8
Black  
White  
Red  
White  
Green  
Blue  
White  
3 POLES  
L
White  
1
2
One  
Two  
3
4
Three  
Four  
Yellow  
Gray  
Orange  
N
Q
S
Black  
Black  
R
Black  
4 CIRCUIT  
1
A
B
Switch Only (no coil)  
Series Trip (current)  
10 APPLICATION RATING  
5
B
D
H
M
125 VDC  
240 VAC  
480 VAC  
80 VDC  
4
3
5 AUXILIARY / ALARM SWITCH  
0
1
3
5
6
without Aux Switch  
S.P.D.T., Screw Terminal  
S.P.D.T. Screw Terminal (Gold Contacts)  
Plug-in Terminal  
Plug-in Terminal (Gold Contacts)  
11 AGENCY APPROVAL  
A
C
E
Without Approvals  
UL Recognized, CSA Accepted  
UL Recognized, CSA Accepted, TUV Certified, CCC Certified  
6 FREQUENCY & DELAY  
03 Switch Only  
10 DC, Instantaneous  
11 DC, Ultra Short  
12 DC, Short  
14 DC, Medium  
16 DC, Long  
20 50/60 Hz Instantaneous  
21 50/60 Ultra Short  
22 50/60 Hz Short  
24 50/60 Hz Medium  
Notes:  
26 50/60 Hz Long  
1
Switch only circuit only available when tied to a protected pole (Circuit code B)  
- for .2 to 30 amps select current code 630  
2
42 50/60 Hz High-inrush Short  
44 50/60 Hz High-inrush Medium  
46 50/60 Hz High-inrush Long  
52 DC High-inrush Short  
- for 31 to 50 amps select current code 650  
- for 51 to 63 amps select current code 663  
- Use delay 03 for all switch only poles  
2
3
Hi Inrush Delays limited to 50A max  
54 DC High-inrush Medium  
56 DC High-inrush Long  
On multi-pole breakers one auxiliary switch is supplied , mounted in the extreme  
left pole when viewed from front of panel  
480 VAC rating requires 3 or 4 pole break 3Φ and 2 pole break 1Φ  
This construction is polarity sensitive when constructed as a single pole unit,  
125 VDC is only available without agency approvals  
4
5
7 CURRENT RATING (AMPERES)  
CODE AMPERES  
210 0.100  
220 0.200  
225 0.250  
230 0.300  
235 0.350  
240 0.400  
245 0.450  
250 0.500  
255 0.550  
260 0.600  
265 0.650  
270 0.700  
275 0.750  
280 0.800  
285 0.850  
290 0.900  
410 1.000  
512 1.250  
415 1.500  
517 1.750  
420 2.000  
522 2.250  
425 2.500  
527 2.750  
430 3.000  
435 3.500  
440 4.000  
445 4.500  
450 5.000  
455 5.500  
460 6.000  
465 6.500  
470 7.000  
475 7.500  
480 8.000  
485 8.500  
490 9.000  
495 9.500  
610 10.000  
710 10.500  
611 11.000  
711 11.500  
612 12.000  
712 12.500  
613 13.000  
614 14.000  
615 15.000  
616 16.000  
617 17.000  
618 18.000  
620 20.000  
622 22.000  
624 24.000  
625 25.000  
630 30.000  
635 35.000  
640 40.000  
650 50.000  
655 55.000  
660 60.000  
663 63.000  
Email: sales@carlingtech.com Application Support: team2@carlingtech.com  
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com  
|
5
G-Series Circuit Breaker - DIN Rail – UL489 – Ordering Scheme  
G A 1 B 0 24 620 1 1 D G  
8
9
10  
Rating  
11  
Agency  
Approval  
1
2
3
4
5
6
7
Terminal  
Actuator  
Color &  
Legend  
Series  
Actuator  
Poles  
Circuit  
Aux/Alarm  
Switch  
Frequency  
& Delay  
Current Rating  
1 SERIES  
G
8 TERMINAL  
1
Screw Terminal  
2 ACTUATOR  
9 ACTUATOR COLOR & LEGEND  
A
S
Handle, one per pole  
Actuator Color  
White  
ON-OFF Dual  
Legend Color  
Black  
1
Mid-Trip Handle, one per pole  
B
D
G
J
1
2
3
4
5
6
7
8
Black  
White  
Red  
White  
Green  
Blue  
Yellow  
Gray  
White  
3 POLES  
L
White  
1
2
3
One  
N
Q
S
Black  
Two  
Black  
Three  
Orange  
Black  
4 CIRCUIT  
B
Series Trip (current)  
10 APPLICATION RATING  
5
B
C
D
K
M
125 VDC  
6
120/240 VAC  
3
7
5 AUXILIARY / ALARM SWITCH  
240 VAC  
8
0
1
3
5
6
without Aux Switch  
S.P.D.T., Screw Terminal  
S.P.D.T. Screw Terminal (Gold Contacts)  
Plug-in Terminal  
Plug-in Terminal (Gold Contacts)  
120 VAC  
9
80 VDC  
11 AGENCY APPROVAL  
A
G
Without Approvals  
UL489 Listed  
6 FREQUENCY & DELAY  
11 DC, Ultra Short  
12 DC, Short  
14 DC, Medium  
16 DC, Long  
21 50/60 Ultra Short  
22 50/60 Hz Short  
24 50/60 Hz Medium  
26 50/60 Hz Long  
4
42 50/60 Hz High-inrush Short  
44 50/60 Hz High-inrush Medium  
Notes:  
4
1
2
3
Mid-trip Handle(s) available at 1 pole unit and 2 pole unit only.  
Third pole of a 3 pole unit is switch only pole.  
4
46 50/60 Hz High-inrush Long  
4
On multi-pole breakers one auxiliary switch is supplied, mounted in the extreme left  
pole when viewed from front of panel.  
52 DC High-inrush Short  
4
54 DC High-inrush Medium  
4
5
6
Hi Inrush Delays limited to 50A maximum.  
125VDC for 2 pole unit only.  
4
56 DC High-inrush Long  
120/240VAC for 2 pole and 3 pole unit only. Limited to 50A maximum, and third pole  
of a 3-pole unit is switch only pole.  
7
8
9
240VAC for 1 pole unit only, limited to 25A maximum  
120VAC for 1 pole unit only, limited to 50A maximum.  
80VDC for 1 pole unit only  
7 CURRENT RATING (AMPERES)  
CODE AMPERES  
410 1.000  
512 1.250  
415 1.500  
517 1.750  
420 2.000  
522 2.250  
425 2.500  
527 2.750  
430 3.000  
435 3.500  
440 4.000  
445 4.500  
450 5.000  
455 5.500  
460 6.000  
465 6.500  
470 7.000  
475 7.500  
480 8.000  
485 8.500  
490 9.000  
495 9.500  
610 10.000  
710 10.500  
611 11.000  
711 11.500  
612 12.000  
712 12.500  
613 13.000  
614 14.000  
615 15.000  
616 16.000  
617 17.000  
618 18.000  
620 20.000  
622 22.000  
624 24.000  
625 25.000  
630 30.000  
635 35.000  
640 40.000  
650 50.000  
Email: sales@carlingtech.com Application Support: team2@carlingtech.com  
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com  
|
6
G-Series Circuit Breaker - DIN Rail - UL Recognized – Dimensional Specifications  
Dimensional Specifications: in. [mm]  
1 POLE WITHOUT AUXILIARY SWITCH  
1 POLE WITH AUXILIARY SWITCH  
(PLUG-IN TERMINAL BLOCK)  
1 POLE WITH AUXILIARY SWITCH  
(SCREW TERMINAL BLOCK)  
MULTIPLE POLES WITH AUXILIARY SWITCH (PLUG-IN TERMINAL BLOCK)  
Notes:  
1
2
All dimensions are in inches [millimeters].  
Tolerance ±.020 [.51] unless otherwise specified.  
Email: sales@carlingtech.com Application Support: team2@carlingtech.com  
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com  
|
7
G-Series Circuit Breaker - DIN Rail - UL489 – Dimensional Specifications  
Dimensional Specifications: in. [mm]  
1 POLE WITH AUXILIARY SWITCH (PENDING)  
1 POLE WITHOUT AUXILIARY SWITCH  
(PLUG-IN TERMINAL BLOCK)  
1 POLE WITH AUXILIARY SWITCH (PENDING)  
(SCREW TERMINAL BLOCK)  
MULTIPLE POLES WITH AUXILIARY SWITCH (PENDING) (PLUG-IN TERMINAL BLOCK)  
Notes:  
1
2
All dimensions are in inches [millimeters].  
Tolerance ±.020 [.51] unless otherwise specified.  
Email: sales@carlingtech.com Application Support: team2@carlingtech.com  
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com  
|
8
G-Series Circuit Breaker - DIN Rail – Mounting / Connector Specifications  
UL RECOGNIZED  
UL489  
Email: sales@carlingtech.com Application Support: team2@carlingtech.com  
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com  
|
9
Sales Representatives, Distributors & Company Profile  
Authorized Sales Representatives and Distributors  
Click on a region of the map below to find your local representatives and distributors or visit  
www.carlingtech.com/findarep.  
CANADA  
EUROPE  
USA  
MIDDLE  
EAST  
MEXICO  
AFRICA  
ASIA-PACIFIC  
OCEANIA  
SOUTH  
AMERICA  
About Carling  
Founded in 1920, Carling Technologies is a leading manufacturer of electrical and electronic switches  
and assemblies, circuit breakers, electronic controls, power distribution units, and multiplexed power  
distribution systems. With four ISO registered manufacturing facilities and technical sales offices worldwide,  
Carling Technologies Sales, Service and Engineering teams do much more than manufacture electrical  
components, they engineer powerful solutions! To learn more about Carling please visit  
www.carlingtech.com/company-profile.  
To view all of Carling’s environmental, quality, health & safety certifications please visit  
www.carlingtech.com/environmental-certifications  
Email: sales@carlingtech.com Application Support: team2@carlingtech.com  
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com  
Worldwide Headquarters  
Carling Technologies, Inc.  
60 Johnson Avenue, Plainville, CT 06062  
Phone: 860.793.9281 Fax: 860.793.9231  
@
Email: sales carlingtech.com  
@
Northern Region Sales Office: nrsm carlingtech.com  
@
Southeast Region Sales Office: sersm carlingtech.com  
@
Midwest Region Sales Office: mrsm carlingtech.com  
@
West Region Sales Office: wrsm carlingtech.com  
@
Latin America Sales Office: larsm carlingtech.com  
Asia-Pacific Headquarters  
Carling Technologies, Asia-Pacific Ltd.,  
Suite 1607, 16/F Tower 2, The Gateway,  
Harbour City, 25 Canton Road,  
Tsimshatsui, Kowloon, Hong Kong  
Phone: Int + 852-2737-2277 Fax: Int + 852-2736-9332  
@
Email: sales carlingtech.com.hk  
@
Shenzhen, China: shenzhen carlingtech.com  
@
Shanghai, China: shanghai carlingtech.com  
@
Pune, India: india carlingtech.com  
@
Kaohsiung, Taiwan: taiwan carlingtech.com  
@
Yokohama, Japan: japan carlingtech.com  
|
|
Europe Middle East Africa Headquarters  
Carling Technologies LTD  
4 Airport Business Park, Exeter Airport,  
Clyst Honiton, Exeter, Devon, EX5 2UL, UK  
Phone: Int + 44 1392.364422 Fax: Int + 44 1392.364477  
@
Email: ltd.sales carlingtech.com  
@
Germany: gmbh carlingtech.com  
@
France: sas carlingtech.com  
www.carlingtech.com  
REV_01_2019  

相关型号:

GA2-B1-12-440-11-ME

Magnetic Circuit Breaker, 2 Pole(s), 4A, 80VDC, Din-rail Mount,
Carling Techn

GA2-B1-12-445-11-ME

Magnetic Circuit Breaker,
Carling Techn

GA2-B1-12-616-11-ME

Magnetic Circuit Breaker, 2 Pole(s), 16A, 80VDC, Din-rail Mount,
Carling Techn

GA2-B1-12-640-11-ME

Magnetic Circuit Breaker,
Carling Techn

GA2-B1-22-420-11-DE

Magnetic Circuit Breaker, 2 Pole(s), 2A, 240VAC, Din-rail Mount,
Carling Techn

GA2-B1-22-625-11-DE

Magnetic Circuit Breaker, 2 Pole(s), 25A, 240VAC, Din-rail Mount,
Carling Techn

GA2-B1-44-425-11-DE

Magnetic Circuit Breaker, 2 Pole(s), 2.5A, 240VAC, Din-rail Mount,
Carling Techn

GA2-B1-44-440-11-DE

Magnetic Circuit Breaker, 2 Pole(s), 4A, 240VAC, Din-rail Mount,
Carling Techn

GA2-B1-44-613-11-DE

Magnetic Circuit Breaker, 2 Pole(s), 13A, 240VAC, Din-rail Mount,
Carling Techn

GA20-3G302H

RESISTOR, TEMPERATURE DEPENDENT, NTC, 3000ohm, THROUGH HOLE MOUNT
MITSUBISHI

GA20-3H103H

RESISTOR, TEMPERATURE DEPENDENT, NTC, 10000ohm, THROUGH HOLE MOUNT
MITSUBISHI

GA20-3U503H

RESISTOR, TEMPERATURE DEPENDENT, NTC, 50000ohm, THROUGH HOLE MOUNT
MITSUBISHI